Kilowatts to Amps Calculator

Convert kilowatts to amps for DC, single-phase, and three-phase circuits.

RESULT — CURRENT
Formula: A = (kW × 1,000) ÷ V

How do you convert kilowatts to amps?

Multiply kilowatts by 1000, then divide by volts. A 5 kW single-phase load at 240 V draws (5 × 1000) ÷ 240 = 20.8 A. For three-phase, divide by (√3 × V × PF): a 5 kW, 400 V, PF 0.9 motor draws 5000 ÷ (1.732 × 400 × 0.9) = 8.0 A.

kW to Amps Formula

DC (Direct Current)
A = (kW × 1,000) ÷ V

For DC circuits, simply multiply kW by 1,000 to get watts, then divide by voltage. Power factor does not apply to DC.
Example: 2 kW at 120 V to (2 × 1,000) ÷ 120 = 16.6667 A.

AC Single-phase
A = (kW × 1,000) ÷ (V × PF)

For single-phase AC circuits, divide real power by voltage and power factor. A lower PF means more current is drawn for the same useful power output.
Example: 3 kW at 230 V, PF 0.85 to (3 × 1,000) ÷ (230 × 0.85) = 15.3374 A.

AC Three-phase — Line-to-Line Voltage
A = (kW × 1,000) ÷ (√3 × VLL × PF)

Use this formula when the voltage given is line-to-line (phase-to-phase), which is the standard way to specify three-phase voltage (e.g. 208 V, 400 V, 480 V). √3 ≈ 1.7321.
Example: 10 kW at 400 V (L-L), PF 0.9 to (10 × 1,000) ÷ (1.7321 × 400 × 0.9) = 16.0375 A.

AC Three-phase — Line-to-Neutral Voltage
A = (kW × 1,000) ÷ (3 × VLN × PF)

Use this formula when using the line-to-neutral (phase-to-neutral) voltage. Note: VLN ≈ VLL ÷ √3, so both three-phase formulas give the same result for the same physical system.
Example: 10 kW at 231 V (L-N), PF 0.9 to (10 × 1,000) ÷ (3 × 231 × 0.9) = 16.0375 A (same as 400 V L-L example above, since 400 ÷ √3 ≈ 231 V).

kW to Amps Reference Table

All values assume unity power factor (PF = 1.0). For other PF values, use the calculator above.

kW 120 V 208 V 240 V 277 V 480 V
1 kW 8.3333 A 4.8077 A 4.1667 A 3.6101 A 2.0833 A
2 kW 16.6667 A 9.6154 A 8.3333 A 7.2202 A 4.1667 A
3 kW 25.0000 A 14.4231 A 12.5000 A 10.8303 A 6.2500 A
5 kW 41.6667 A 24.0385 A 20.8333 A 18.0505 A 10.4167 A
7.5 kW62.5000 A 36.0577 A 31.2500 A 27.0758 A 15.6250 A
10 kW 83.3333 A 48.0769 A 41.6667 A 36.1011 A 20.8333 A
15 kW 125.0000 A72.1154 A 62.5000 A 54.1516 A 31.2500 A
20 kW 166.6667 A96.1538 A 83.3333 A 72.2022 A 41.6667 A
25 kW 208.3333 A120.1923 A104.1667 A90.2527 A 52.0833 A
30 kW 250.0000 A144.2308 A125.0000 A108.3032 A62.5000 A
50 kW 416.6667 A240.3846 A208.3333 A180.5054 A104.1667 A

Single-phase vs Three-phase vs Power Factor

Single-phase (1Ø)

One live conductor and a neutral. Standard for homes, small offices, and loads up to about 10 kW. For the same power, single-phase draws more current per conductor than three-phase.

A = (kW × 1,000) ÷ (V × PF)
Three-phase (3Ø)

Three conductors, each offset 120°. Used in industrial and commercial buildings for motors, HVAC, and large equipment. For the same kW, three-phase requires less current per conductor than single-phase.

A = (kW × 1,000) ÷ (√3 × V × PF)
Power Factor (PF)

PF measures how efficiently a circuit converts apparent power (kVA) to real power (kW). Resistive loads (heaters, incandescent bulbs) have PF = 1.0. Inductive loads (motors) typically have PF ≈ 0.8. General commercial: PF ≈ 0.9. A lower PF means higher current.

PF = kW ÷ kVA

Frequently Asked Questions

How do I convert kW to amps?

Use the formula for your circuit type:

  • DC: A = (kW × 1,000) ÷ V
  • AC single-phase: A = (kW × 1,000) ÷ (V × PF)
  • AC three-phase (L-L voltage): A = (kW × 1,000) ÷ (√3 × V × PF), where √3 ≈ 1.7321
  • AC three-phase (L-N voltage): A = (kW × 1,000) ÷ (3 × V × PF)

For DC circuits, power factor does not apply. For AC, use PF = 1.0 for resistive loads and PF = 0.8 for typical motors.

How many amps is 1 kW at 120V?
  • DC at 120 V: (1 × 1,000) ÷ 120 = 8.3333 A
  • AC single-phase at 120 V, PF 0.8: (1 × 1,000) ÷ (120 × 0.8) = 10.4167 A

The AC value is higher because a power factor below 1.0 means additional reactive current is drawn that does not contribute to real power.

What is the difference between kW and kVA?

kW (kilowatts) is real (active) power — the actual energy doing useful work, such as heat, light, or mechanical motion. kVA (kilovolt-amps) is apparent power, which is the total power drawn by the circuit including reactive power. They are related by: kW = kVA × PF.

For purely resistive loads (electric heaters, incandescent bulbs), PF = 1.0, so kW = kVA. For motors and other inductive loads, kVA > kW. When sizing cables and breakers for AC circuits, use the current calculated from kVA (or from kW ÷ PF) to account for the full apparent power.

How many amps is 5 kW at 240V three-phase?
  • Three-phase L-L at 240 V, PF 0.8: (5 × 1,000) ÷ (1.7321 × 240 × 0.8) = 15.0361 A
  • Three-phase L-L at 240 V, PF 1.0: (5 × 1,000) ÷ (1.7321 × 240) = 12.0281 A
What size wire do I need for a 5 kW load?

Wire sizing depends on current (amps), not directly on watts. At 240 V single-phase with PF = 1.0, 5 kW draws (5 × 1,000) ÷ 240 = 20.83 A.

Per NEC 210.20, continuous loads must be sized at 125%: 20.83 × 1.25 = 26.04 A minimum breaker rating. This requires 10 AWG copper wire (rated 30 A) for most installations. If PF = 0.8, current rises to 26.04 A, and 125% = 32.55 A — requiring 8 AWG copper. Always consult a licensed electrician for actual installation decisions.